High-quality warehouse ventilation is necessary to ensure occupational safety and optimal storage conditions for products. When equipping a ventilation system, it is necessary to adhere to the established norms of the frequency of air exchange, and choose equipment whose parameters correspond to the regulated requirements.
Before proceeding with the design of the engineering network, you should study the principles, as well as find out how to arrange warehouse ventilation, agree?
We will tell you about the features of the organization of natural and forced air exchange, list the requirements for equipment, and also give the normalized microclimate parameters for warehouses for various purposes.
Basic principles for warehouse ventilation
Code of rules SP 60.13330.2012 “SNiP 41-01-2003. Heating, ventilation and air conditioning ”is the main document that spells out the requirements for the organization of ventilation of the premises for the storage of products used in household equipment, building materials and other products.
Features of natural air exchange
Natural air exchange in the warehouse occurs due to the difference in static pressure of the different-temperature air columns. The colder street air enters the room through the air inlet, and the internal air exits through the hood.
In the warm period, the supply openings are located at a level of 0.3 to 1.8 m. In cold weather, they are arranged at a distance from the floor of at least 3 m with a total room height of up to 6 m, and 4 m with a larger room height.
If the warehouse height is small, it is possible to design a lower position of the holes, however, it is necessary to take into account the possibility of covering it with snow and take measures to prevent such a scenario.
Natural ventilation is almost impossible if it is necessary to process the incoming air. Cleaning it from dust through filters, heating or humidification creates resistance in the supply duct and significantly reduces the flow rate.
With natural ventilation, the main problem is the dependence of the flow rate on the parameters of the external environment. In case of excess air intake, the flaps of a manual or automatic type of action are mounted on the holes.
Insufficient air circulation can be partially compensated by installing a ventilation deflector. A more effective way is the installation of forced ventilation.
With natural ventilation, exhaust openings on the roof of the warehouse building are installed in such a way as to obtain the maximum possible draft
Use of forced ventilation
According to paragraphs 7.1.3-7.1.4. a ventilation device, the functioning of which requires mechanical stimulation, is installed in the following cases:
- if the necessary microclimate parameters cannot be achieved with natural air circulation;
- if at a certain time of the year there are such temperature and humidity characteristics of the outdoor air that natural ventilation does not provide the required microclimate in the warehouse;
- in the presence of rooms or their zones without natural ventilation.
The placement of exhaust openings must be carried out in the most contaminated parts of the warehouse. In the case of a non-zero balance of the volume of transported air, its compensation occurs due to the process of infiltration through the walls and roof of the structure.
Usually colder fresh air spreads along the bottom of the room, forcing the polluted up. In this case, the exhaust openings are placed under the ceiling of the warehouse
The use of forced ventilation leads to the need to purchase and install expensive systems, as well as constant costs for electricity, equipment maintenance and activities aimed at compensating for its wear.
Therefore, combined natural and forced air exchange is often used. The operation of mechanical devices is used to compensate for the difference between the required volume of replaced air and ventilation capabilities.
Uncontrolled air exchange through infiltration
When calculating the parameters of the equipment used to create the required microclimate, it is necessary to take into account air infiltration through the warehouse perimeter. The presence of leaks in the structures leads to uncontrolled inflow and outflow of air.
If compliance with a certain temperature and humidity is not necessary, then sometimes you can completely abandon any means of organizing ventilation in favor of infiltration.
However, if it is necessary to create a certain microclimate, uncontrolled air exchange creates problems. This is due to inconsistent environmental parameters and the volume of incoming air.
At minus temperatures, the exit of a warm stream through the slots promotes the formation of condensate and ice. This is fraught with the gradual destruction of load-bearing structures, the formation of fungus and mold, an increased risk of short circuit and other problems.
The heat loss of any building is easily determined using infrared photography. In this way, you can identify places of intense infiltration and take measures to eliminate it.
Since the volume of infiltration is unstable and depends on many parameters, it is not taken into account in the normative calculation of air exchange. However, it appears with some assumptions when calculating heat loss and modeling the moisture index.
If infiltration in warehouses is undesirable, then it is necessary to eliminate the prerequisites for its occurrence. In addition to the presence of gaps in the walls of the building, there are other reasons leading to unaccounted air exchange.
On the windward side there is a dynamic pressure of the air mass on the wall of the building and the penetration of air into the room. Therefore, when designing warehouses, it is necessary to take into account the wind rose and not position the wall of the building perpendicular to the prevailing direction.
An effective solution to the problem can also be the installation of wind defenses.
On the lateral and leeward sides, the wind pressure is negative. As a result of the resulting difference, conditions are created for the outflow of air from the room.
To minimize the pressure gradient, it is necessary to adhere to the recommendations on the geometric parameters of roofs and to eliminate the separation points of the boundary layer of the flow by installing wind-guiding elements.
The internal reason for the occurrence of infiltration may be the difference in the amount of supply and exhaust air. The unbalanced operation of the ventilation system leads to compensation for the missing or excess volume due to infiltration.
Therefore, periodic calibration of fans, cleaning of air ducts and filters, as well as other preventive maintenance are necessary.
A dirty ventilation filter is the most common cause of reduced system performance. Most of them are easy to clean, which requires minimal time.
Requirements for the installed equipment
Ventilation equipment works in conjunction with other devices to create and maintain conditions for normal functioning and technical condition of the warehouse. Therefore, it is necessary not only to comply with the requirements specified in SP 60.13330.2012, but also to take into account the provisions of other regulatory documents.
Basic rules for equipment placement
The power of ventilation equipment must be selected based on the estimated air circulation, taking into account possible volume losses due to incomplete tightness of the system.
In small warehouses, equipment is placed on the basis of the following principles:
- accessibility and convenience of preventive and repair work;
- compliance with fire and electrical safety requirements;
- availability of free space.
In large warehouses where compliance with standards is required, equipment is installed in a special room or on the roof of a building. It depends on the classification of the warehouse in certain categories of fire hazard.
If ventilation equipment is installed on the roof of the building, then it is necessary to limit access to it by unauthorized persons. This requirement is spelled out in SP 60.13330.2012
Standby and emergency ventilation systems
In the event of a breakdown of the ventilation equipment and system shutdown, an emergency situation in the warehouse may occur. A prolonged lack of air exchange can lead to damage to stored products and to the creation of conditions for a high concentration of undesirable impurities in the air.
Therefore, normative documents spell out the procedure for installing backup systems and their parameters.
According to clause 7.2.8, if people are supposed to stay permanently in the warehouse premises, then the air exchange systems must be equipped with redundant fans or two or more units are used.
According to clause 7.2.18, in rooms with a capacity of more than 10 tons and a high fire hazard category, it is necessary to provide a backup system that fully meets the need for air exchange.
An emergency situation with the release of a large amount of pollutants is also possible at the warehouse. Solve the problem will help short-term operation of the ventilation system in forced mode. Effective work is demonstrated by aspiration systems.
According to clause 7.6.1, the air flow rate and other parameters of the emergency system are determined on the basis of the provisions of the technological part of the project.
Hoods to remove the contaminant are placed depending on its density. If volatile components are heavier than air, then the nozzles are installed in the working area, and if it is lighter, then under the ceiling.
A dust suspension not only adversely affects human health. Flour and wood dust are explosive, therefore the installation and operation of emergency ventilation must be checked by the fire department
Microclimate devices
The most effective way to ensure the temperature and humidity regime is to integrate air heaters and humidifiers into the supply ventilation. In this case, air will be supplied with predefined parameters.
Heaters can be of electric and water type. The second are more common for ventilation systems of warehouses and large complexes.
During a year with characteristic subzero temperatures, the use of heat recovery systems is relevant. This solution significantly reduces the cost of heating the warehouse.
Due to the presence of a separate zone for equipment, when choosing a recuperator or regenerator, you can only be guided by the financial costs and efficiency of the system. Noise level and mass of devices are not so important as when using them in apartment ventilation.
Rotary recuperators and water heaters have built-in or external electric motors. According to clause 7.2.7, it is necessary for them to provide backup motors and pumps in case of breakdown of the main components.
A rotary recuperator makes a noise, but for a warehouse this is not as important as high efficiency. Therefore, the use of this type of device is a popular solution for the ventilation of non-residential premises
Climate parameters for typical warehouses
The microclimate parameters in warehouses and the air exchange rate are prescribed in NTP-APK 1.10.17.001-03 “Norms for technological design of bases and general-purpose warehouses for resource support enterprises”, as well as in industry documents.
So, for example, the air environment parameters of a food warehouse depend on storage conditions and the nomenclature of specific products.
The concept of air exchange rate
Warehouse air exchange is necessary to achieve two goals:
- creation of a special microclimate of the premises optimal for storing this type of product;
- removal of harmful, explosive and other impurities and aerosols from the premises.
The calculation of the frequency of air exchange is performed according to the formula:
K (1 / h) = A / V,
Where:
- A - the volume of incoming air in one hour, (m3/ h);
- V - warehouse volume, (m3).
For the storage of most types of products, normative documents prescribe a ventilation rate equal to one. With non-commercial use of the premises as a warehouse, often this figure is significantly lower. This is justified if ventilation of such power is guaranteed to provide the necessary indicators of temperature and humidity.
When commercial activities are required to comply with the requirements of regulatory documents on ventilation.
The total capacity of the installed systems should provide the air circulation of the necessary multiplicity. Otherwise, it is impossible to obtain a positive opinion from Rospotrebnadzor and the fire inspection on the intended use of the warehouse.
Checking compliance of ventilation parameters with regulatory requirements is the responsibility of the fire inspector. If violations are detected, the warehouse may be suspended until they are eliminated.
If there are several types of products in stock, it is necessary to provide microclimate parameters that satisfy the storage conditions of each of them.
Storage of building materials and products
When storing most types of building materials, the temperature regime of the room can be unregulated. Warehouses with rolled waterproofing bitumen-polymer and polymer materials used in the arrangement of roofs, foundations and walls of rooms with an unusually high level of moisture fall under the exception.
The air temperature in this case should not be lower than +50C.
Humidity in warehouses of this type is not standardized, except for the case of storage of bulk building materials. Do not allow moisture and contamination of cement, graphite and gypsum. Permissible relative humidity during storage is determined by the manufacturer and depends on the material and the method of its packaging.
Air circulation for sanitary-technical and sanitary-ceramic products is not standardized. For building materials, the required air exchange rate is taken to be equal to one.
Features of wood storage
There are no general regulatory documents governing the performance of air in a timber warehouse. The main criteria when choosing ventilation is the humidity permissible for a particular type of material or finished product.
If the specificity of production involves the simultaneous receipt of a large amount of raw wood, then it is necessary to have forced ventilation, which is used immediately after loading the product. When the material reaches its natural moisture index, mechanical blowing is turned off.
In the storage rooms with lumber, the microclimate is constantly monitored, using special instruments for checking humidity.
For uniform ventilation of wood and products based on it, their proper storage is necessary. It is necessary to observe the procedure for laying round wood and lumber in stacks.
Without proper stacking, it is not possible to dry the wood to the required levels. Air must penetrate the array, otherwise the tree will rot with any ventilation
When transporting small items, the tight packing method is often used with space saving.After receiving such products in the warehouse, it must be decomposed or scattered so that all components are formed air access into the heap.
Otherwise, with high humidity of the material, favorable conditions will arise for the formation of fungus and mold.
Often a warehouse is equipped in the warehouse for primary processing of wood - sawing round logs or sawing edges. As a result of these works, wood dust of various sizes is released into the air. Her constant inhalation is a common non-infectious factor in the appearance of chronic bronchitis.
If dust is removed using general ventilation, the entire warehouse will become contaminated over time. Therefore, they provide for the installation of local chip and dust extractors of the cyclonic type with a separate hood, if such devices are not included in the set of woodworking equipment.
Storage of metal and equipment
For metal products, such as pipes, faucets, valves, temperature and humidity indicators are not standardized.
Colored and black metal is not demanding on temperature and humidity. Ventilation is necessary to ensure safe working conditions.
Electrical equipment and spare parts for internal combustion engines must be stored in compliance with anti-corrosion conditions.
Hand-held power tools, metal cutting and bench tools are stored at a temperature not lower than + 5 ° С and air humidity up to 70%.
For complex equipment, such as woodworking machines, manufacturers give recommendations on the temperature and humidity conditions during their conservation.
These requirements must be strictly adhered to, because complex units contain elements created using combinations of different materials, the properties of which can change if stored improperly.
Often the processing of metal products and equipment from corrosion is carried out directly in the warehouse. When performing it in order to avoid exposure to an increased concentration of toxic fumes, it is necessary to ventilate the room for 1-1.5 days.
In rooms where flammable and explosive substances are stored, smoke ventilation should be additionally provided.
The video demonstrates the organization of ventilation of a warehouse complex:
Installation device for removing sawdust in a separate hood:
Strict adherence to the requirements of regulatory documents for the ventilation of a warehouse will create the microclimate necessary for high-quality storage of products.